R-101 found installed.

Image
 

not an ideal location for smoke detector.

Image
 

Foam solution piping hanger failure.

Image
 

Hanger failure.

Image
 

Hanger failure, embedment of coach screws

Image
 

Diesel engine raw water line pipe support failure

Image
 

Poor location of smoke detector.

Image
 

top side FP water tank visual inspection

Image
 

Unable to open gravity concrete tank storage access hatch. Corrosion.

Image
 

R-102 missing screws.

Image
 

WPIV handwheel missing.

Image
 

Unsure if digital pressure gauge was listed.

Image
 

Wall post indicator valve, mechanical impact damage

Image
 

Examining water level indicator

Image
 

Interior of fire protection water storage tank, temp and level sensors shown. Damaged ladder. Low water level.

Image
 

Another altitude valve found out of service.

Image
 

No drain on RPZ domestic backflow.

Image
 

Improper support of fire alarm conductor.

Image
 

Wire nuts used on UFC 03-600-1. Box cover missing.

Image
 

Bent handle on pressure gauge.

Image
 

Hose valve handle missing.

Image
 

Extinguisher obstructed

Image
 

All dry pipe accelerators found out of service.

Image
 

Ladder missing. Possible wildland fire risk due to vegetation.

Image
 

Wire rope disconnected from tank level indicator

Image
 

Non-standard fitting on hose valve.

Image
 

Zebra Mussel 2007 and 2023 maps.

Image
 

fire alarm module not properly mounted, some corrosion is noted.

Image
 

Corroded unistrut mount.

Image
 

No suction pressure gauge installed on fire pump

Image
 

Diesel engine cooling line y-strainer leak

Image
 

Pump skid not grouted.

Image
 

Storage in electrical room, panels blocked.

Image