Debris recovered during fire hydrant annual flow test - East Africa.
- Get link
- X
- Other Apps
ITC valve cannot be fully opened due to interference with wall. Accepted, commissioned and approved install. Florida, USA
- Get link
- X
- Other Apps
Analysis of steel bolted uninsulated 100,000 gallon water storage tank located above grade in a winter environment and the amount of energy needed for a water injection boiler system. The tank exhibited freezing ice on exterior of tank and on surface of water inside tank. The boiler installed was only 40 kw. Undersized from day one. Tank is located 22 km south of the Baltic Ocean.
- Get link
- X
- Other Apps
Evidence of prior leak/freeze up noted on wall of fire sprinkler riser room
- Get link
- X
- Other Apps
2nd corrosion control cabinet, also shows internal damage from water infiltration after 18 month exposure to tropical environment.
- Get link
- X
- Other Apps
Corrosion control for steel bolted fire protection water storage tank. Control cabinet shows evidence of water infiltration. Controller installed on exterior of water storage tank and subject to tropical weather exposures. At time of photograph, unit approximately 18 months old.
- Get link
- X
- Other Apps
Deficiency, missing cap. Design/install error - missing pressure gauge.
- Get link
- X
- Other Apps
Deficiency. Also note clearance from handwheel to column
- Get link
- X
- Other Apps
Deficiency corrosion and non-axial loads on pipe hanger
- Get link
- X
- Other Apps
Corroded high pressure CO2 fire suppression system components
- Get link
- X
- Other Apps
Fire door has been field painted. Note the frame listing label on the right.
- Get link
- X